| Input | |
| Voltage | 400 Vac |
| Tolerance | 320 – 450V |
| Frequency | 50Hz ± 6% |
| Output | |
| Voltage | 400Vac ± 1% |
| Power Factor | 0.8 |
| Transfer Time | 0 ms |
| Frequency | 50Hz ± 6% (On Mains) |
| 50Hz ± 0.5% (On Battery) | |
| Waveform | Pure Sine Wave |
| THDi | Linear Load ≤ 3%; Non-linear Load ≤ 5% |
| Crest Factor | 3 : 1 (Max) |
| Bypass Facility | Maintenance Bypass and Static Bypass |
| DC Bus / DC Functions: | |
| DC Bus Voltage | 384V |
| Charging Current | 5 – 20A, Adjustable |
| Cold-Start Function | Yes |
| Battery Charging in OFF Mode | Yes |
| Battery Type | Sealed, Maintenance-free VRLA |
| LCD User Interface: | |
| Metering / Indications for | Voltage |
| Load % | |
| Frequency | |
| General Status | |
| Alarm | |
| Communication: | |
| Interfaces | RS232 |
| Overload | |
| 105~125% | 10 mins (Output swithes to bypass after 60s) |
| >130% | 1 min |
| Environment: | |
| Temperature | 0 ~ 40oC |
| Humidity | 20 ~ 90% Non-condensing |
| Altitude | < 1000m |
| IP Class | 20 |
| Physical: | |
| Dimensions (mm) | 10-20kVA : 560 x 700 x 1040 (W x D x H) |
| 30-40kVA : 660 x 800 x 1380 (W x D x H) | |
| 60-80kVA : 1540 x 880 x 1570 (W x D x H) | |
| 100-200kVA : 2000 x 980 x 1800 (W x D x H) | |
| Weight (Kg) | 10kVA : 260kg |
| 15kVA : 350kg | |
| 20kVA : 400kg | |
| 30kVA : 480kg | |
| 40kVA : 650kg | |
| 60kVA : 650kg | |
| 80kVA : 1200kg | |
| 100kVA : 1330kg | |
| 120-200kVA : On Request | |
UPS, Vectronic Ups
Benita / Pre-sale Questions
Need Help? Contact Us via WhatsApp
3kVA Vectronic Online UPS
Description:
Profie: Tower
Range: 3kVA
Voltage: 400Vac
Frequency: 50Hz
₦260,000 ₦310,000
15kVA Relay stabilizer (95v-280v)
FL-IVPM2512 Li 2.5KVA 12V pure sine wave inverter with 80A MPPT
3.5KVA SOLAR SYSTEM
80A MPPT Solar Charger controller (12V- 48V)
2.5KVA FULL PACKAGE
10kVA Vectronic Online UPS (C Series with batteries)
3.5KVA FULL PACKAGE WITH SMK INVERTER
2.5KVA SOLAR SYSYTEM INSTALLATION
Kartel 10KVA 48V Pure Sine Wave Desktop Inverter
10kVA Vectronic Online UPS FS Series 