Product specifications:
| Input | |
| Voltage | 230 Vac |
| Tolerance | Normal Over-voltage: 10% |
| Withstand Over-voltage: 15% (20% max limit) | |
| Normal Under-voltage: – 20% | |
| Withstand Low-voltage: – 30% (-37% lowest limit) | |
| Power Factor | 0.98 |
| Output | |
| Voltage | 230Vac ± 1% |
| Power Factor | 0.8 |
| 0.9 | |
| Transfer Time | 0 ms |
| Frequency | 46 – 54Hz (On Mains) |
| 50Hz (On Battery) | |
| Waveform | Pure Sine Wave |
| THDi | Linear Load ≤ 3%; Non-linear Load ≤ 6% |
| Crest Factor | 3 : 1 |
| Bypass Facility | FS Model: Static Bypass |
| FS-V Model: Both Maintenance Bypass and Static Bypass | |
| DC Bus / DC Functions: | |
| 1kVA | 36V |
| 2kVA | 72/96V |
| 3kVA | 96V |
| 6/10kVA | 192V / 240V |
| Cold-Start Function | Yes |
| Charging Time | 6hr to recover to 90% capacity |
| Battery Charging in OFF Mode | Yes |
| Battery Type | Sealed, Maintenance-free VRLA |
| LCD User Interface: | |
| Metering / Indications for | Voltage |
| Load % | |
| Frequency | |
| General Status | |
| Alarm | |
| Communication: | |
| Interfaces | RS232, USB*, SNMP* (* Option) |
| Overload | |
| 100~110% | Output swithes to bypass after 60s |
| 125~130% | Output swithes to bypass after 30s |
| >130% | Output swithes to bypass after 100ms |
| Environment: | |
| Temperature | 0 ~ 40oC |
| Humidity | 20 ~ 90% Non-condensing |
| Noise Level | < 50dB from 1m |
| IP Class | 20 |
| Physical: | |
| Dimensions (mm) | 1kVA : 145 x 405 x 220 (W x D x H) |
| 2-3kVA : 192 x 460 x 340 (W x D x H) | |
| 6-10kVA : 248 x 500 x 460 (W x D x H) | |
| Weight (Kg) | 1kVA : 14kg |
| 2kVA : 34kg | |
| 3kVA : 34.5kg | |
| 6kVA : 57kg / 192V: 90kg / 240V | |
| 10kVA : 60kg / 192V; 93kg / 240V | |