Product specifications:
| Input | |
| Voltage | 230 Vac |
| Tolerance | Normal Over-voltage: 10% |
| Withstand Over-voltage: 15% (20% max limit) | |
| Normal Under-voltage: – 20% | |
| Withstand Low-voltage: – 30% (-37% lowest limit) | |
| Power Factor | 0.98 |
| Output | |
| Voltage | 230Vac ± 1% |
| Power Factor | 0.8 |
| 0.9 | |
| Transfer Time | 0 ms |
| Frequency | 46 – 54Hz (On Mains) |
| 50Hz (On Battery) | |
| Waveform | Pure Sine Wave |
| THDi | Linear Load ≤ 3%; Non-linear Load ≤ 6% |
| Crest Factor | 3 : 1 |
| Bypass Facility | FS Model: Static Bypass |
| FS-V Model: Both Maintenance Bypass and Static Bypass | |
| DC Bus / DC Functions: | |
| 1kVA | 36V |
| 2kVA | 72/96V |
| 3kVA | 96V |
| 6/10kVA | 192V / 240V |
| Cold-Start Function | Yes |
| Charging Time | 6hr to recover to 90% capacity |
| Battery Charging in OFF Mode | Yes |
| Battery Type | Sealed, Maintenance-free VRLA |
| LCD User Interface: | |
| Metering / Indications for | Voltage |
| Load % | |
| Frequency | |
| General Status | |
| Alarm | |
| Communication: | |
| Interfaces | RS232, USB*, SNMP* (* Option) |
| Overload | |
| 100~110% | Output swithes to bypass after 60s |
| 125~130% | Output swithes to bypass after 30s |
| >130% | Output swithes to bypass after 100ms |
| Environment: | |
| Temperature | 0 ~ 40oC |
| Humidity | 20 ~ 90% Non-condensing |
| Noise Level | < 50dB from 1m |
| IP Class | 20 |
| Physical: | |
| Dimensions (mm) | 1kVA : 145 x 405 x 220 (W x D x H) |
| 2-3kVA : 192 x 460 x 340 (W x D x H) | |
| 6-10kVA : 248 x 500 x 460 (W x D x H) | |
| Weight (Kg) | 1kVA : 14kg |
| 2kVA : 34kg | |
| 3kVA : 34.5kg | |
| 6kVA : 57kg / 192V: 90kg / 240V | |
| 10kVA : 60kg / 192V; 93kg / 240V | |
2KVA SOLAR SYSTEM
2000VA Vectronic Offline UPS
40kVA Vectronic Online UPS (with batteries)
10kVA Vectronic Online UPS (C Series with batteries)
10kva solar installation with 10kwh lithium battery with panels
3kVA Vectronic Online UPS
3kVA Vectronic Online UPS
1kVA Vectronic Online UPS 