Input |
Voltage |
230 Vac |
Tolerance |
Normal Over-voltage: 10% |
|
Withstand Over-voltage: 15% (20% max limit) |
|
Normal Under-voltage: – 20% |
|
Withstand Low-voltage: – 30% (-37% lowest limit) |
Power Factor |
0.98 |
|
|
Output |
|
Voltage |
230Vac ± 1% |
Power Factor |
0.8 |
|
0.9 |
Transfer Time |
0 ms |
Frequency |
46 – 54Hz (On Mains) |
|
50Hz (On Battery) |
Waveform |
Pure Sine Wave |
THDi |
Linear Load ≤ 3%; Non-linear Load ≤ 6% |
Crest Factor |
3 : 1 |
Bypass Facility |
FS Model: Static Bypass |
|
FS-V Model: Both Maintenance Bypass and Static Bypass |
|
|
DC Bus / DC Functions: |
1kVA |
36V |
2kVA |
72/96V |
3kVA |
96V |
6/10kVA |
192V / 240V |
Cold-Start Function |
Yes |
Charging Time |
6hr to recover to 90% capacity |
Battery Charging in OFF Mode |
Yes |
Battery Type |
Sealed, Maintenance-free VRLA |
|
|
LCD User Interface: |
|
Metering / Indications for |
Voltage |
|
Load % |
|
Frequency |
|
General Status |
|
Alarm |
|
|
Communication: |
|
Interfaces |
RS232, USB*, SNMP* (* Option) |
|
|
Overload |
|
100~110% |
Output swithes to bypass after 60s |
125~130% |
Output swithes to bypass after 30s |
>130% |
Output swithes to bypass after 100ms |
|
|
Environment: |
|
Temperature |
0 ~ 40oC |
Humidity |
20 ~ 90% Non-condensing |
Noise Level |
< 50dB from 1m |
IP Class |
20 |
|
|
Physical: |
|
Dimensions (mm) |
1kVA : 145 x 405 x 220 (W x D x H) |
|
2-3kVA : 192 x 460 x 340 (W x D x H) |
|
6-10kVA : 248 x 500 x 460 (W x D x H) |
Weight (Kg) |
1kVA : 14kg |
|
2kVA : 34kg |
|
3kVA : 34.5kg |
|
6kVA : 57kg / 192V: 90kg / 240V |
|
10kVA : 60kg / 192V; 93kg / 240V |