Input | |
Voltage | 400 Vac |
Tolerance | 320 – 450V |
Frequency | 50Hz ± 6% |
Output | |
Voltage | 400Vac ± 1% |
Power Factor | 0.8 |
Transfer Time | 0 ms |
Frequency | 50Hz ± 6% (On Mains) |
50Hz ± 0.5% (On Battery) | |
Waveform | Pure Sine Wave |
THDi | Linear Load ≤ 3%; Non-linear Load ≤ 5% |
Crest Factor | 3 : 1 (Max) |
Bypass Facility | Maintenance Bypass and Static Bypass |
DC Bus / DC Functions: | |
DC Bus Voltage | 384V |
Charging Current | 5 – 20A, Adjustable |
Cold-Start Function | Yes |
Battery Charging in OFF Mode | Yes |
Battery Type | Sealed, Maintenance-free VRLA |
LCD User Interface: | |
Metering / Indications for | Voltage |
Load % | |
Frequency | |
General Status | |
Alarm | |
Communication: | |
Interfaces | RS232 |
Overload | |
105~125% | 10 mins (Output swithes to bypass after 60s) |
>130% | 1 min |
Environment: | |
Temperature | 0 ~ 40oC |
Humidity | 20 ~ 90% Non-condensing |
Altitude | < 1000m |
IP Class | 20 |
Physical: | |
Dimensions (mm) | 10-20kVA : 560 x 700 x 1040 (W x D x H) |
30-40kVA : 660 x 800 x 1380 (W x D x H) | |
60-80kVA : 1540 x 880 x 1570 (W x D x H) | |
100-200kVA : 2000 x 980 x 1800 (W x D x H) | |
Weight (Kg) | 10kVA : 260kg |
15kVA : 350kg | |
20kVA : 400kg | |
30kVA : 480kg | |
40kVA : 650kg | |
60kVA : 650kg | |
80kVA : 1200kg | |
100kVA : 1330kg | |
120-200kVA : On Request |
UPS, Vectronic Ups
Compare
60kVA Vectronic Online UPS (with batteries)
TMK ENERGIES is the ideal place to shop inverters,stabilizers and any size solar solution you could need for your home and office. we are the major supplier & installer of top quality inverters nationwide at the best prices with more than 2 years warranty. with our broad experience in power solutions, you can say farewell to all power blackouts you encounter daily.
₦10,820,000 ₦10,950,000
Compare